PDU Load Calculator

Check the load on a power strip or circuit in amps and as a percentage of capacity, with the 80% continuous-load limit flagged. Calculates in your browser.

Load on circuit

-

Of full capacity-
Of derated limit-
Safe headroom-

Show the math

Current is load divided by voltage; the rated capacity is voltage × the breaker amps:

amps = watts ÷ volts · safe load ≤ 80% × rating

Electrical code treats a server load as continuous, so a circuit should carry no more than 80% of its breaker rating, a 20 A circuit is good for 16 A. Balance phases and leave headroom for inrush. Calculated entirely in your browser.

What this does

A PDU load calculator checks the load on a power strip or circuit in amps and as a percentage of capacity, flagging the 80% continuous-load limit.

How to use it

  1. Enter the load in watts.
  2. Enter the voltage.
  3. Enter the breaker rating.
  4. Read amps and the 80% headroom check.

How it works

Code treats a server load as continuous, so a circuit should carry no more than 80% of its breaker rating. Headroom absorbs inrush current at power-on.

amps = watts ÷ volts

Understanding your result

The number to respect is the 80 percent continuous-load limit: code treats server loads as continuous, so a 20 A circuit should carry no more than 16 A sustained. The remaining headroom absorbs inrush at power-on and protects against tripping. Balance load across phases and circuits, and never plan to run a circuit at its full nameplate rating.

Example

A 1,920 W load on 120 V draws 16 A — the continuous limit of a 20 A circuit.

Sources & methodology

Last updated .

Frequently asked questions

How do I convert watts to amps?

Divide the load in watts by the voltage. A 1,920 W load on a 120 V circuit draws 16 A.

What is the 80% rule?

Electrical code treats a server load as continuous, so a circuit should carry no more than 80% of its breaker rating. A 20 A circuit is good for a continuous 16 A.

Why leave headroom?

Headroom absorbs inrush current at power-on and lets you balance load across phases, reducing the risk of nuisance breaker trips.